Performance analysis and optimization of high-voltage energy harvesting current transformer (1)
In recent years, as power grids have increasingly advanced toward intelligent and automated operation, real-time monitoring of power systems—such as insulation monitoring of transmission lines, fault location in distribution networks, and overhead line icing detection—has become a critical focus. Given the high voltage levels of transmission lines, monitoring equipment is often exposed to prolonged high-voltage and strong electromagnetic field conditions. To ensure the reliable operation of such equipment, it is essential to provide a highly stable power supply.
Common power supply methods for grid monitoring equipment include battery-based power, solar power, laser power, hybrid power supply, and current transformer (CT)-harvested power.
CT power supply, based on electromagnetic induction from transmission line current, features a simple design, compact size, and low cost. These attributes make it the most widely adopted and popular power supply solution currently available.
Several technical challenges currently exist in CT-based power harvesting:
Insufficient power under low bus current conditions, resulting in a large power dead zone;
Magnetic core saturation under high bus current conditions, leading to distortion of the output voltage waveform;
Significant fluctuations in bus current, which introduce design difficulties in balancing performance between low-current and high-current operation.
Existing Mitigation Strategies
In response to the above issues, various research efforts have proposed and implemented different solutions to partially overcome the limitations of CT energy harvesting:
Combining lithium batteries with CT power supply can, to some extent, address power availability under low-current conditions;
Adopting a dual-core parallel structure with a bypass circuit to extend the operational range of the CT;
Employing a dual magnetic circuit structure with photovoltaic capacitor compensation to reduce the power supply dead zone;
Optimizing magnetic core parameters and adopting a multi-turn winding strategy to prevent core saturation;
Designing a power control circuit using a bidirectional thyristor to accommodate bus current fluctuations within a certain range.
Despite these efforts, the three fundamental issues outlined above remain unresolved.
Emerging Design Solution
Consequently, a novel design approach has been developed. In this design, the magnetic core features an open-gap configuration, which is the most parameter-optimized method for reducing the current dead zone. By analyzing the variations in load and the number of turns, a strategy combining multiple turns with parallel resistors is employed to suppress saturation.
This solution effectively overcomes the challenge of stable power supply under high-current conditions, while also taking low-current power supply requirements into consideration. It offers the advantages of easy installation, straightforward control, and low design cost.
In the following section, we will further analyze: the energy harvesting system based on an open-gap magnetic core, including the optimization of core parameters, the design of anti-saturation measures, and experimental validation of energy harvesting performance.
Categories
New Blog
Call At :
Tel : +86-20-85649266
Fax : +86-20-85649263
Email Us :
Email : derful@coilcore.com
Address :
A402 Zhuangyuangang Industry Park, No.186 Qishan Road, Tianhe District, Guangzhou 510663
© Copyright: 2026 Guangzhou Amorphous Electronic Technology Co.,ltd. All Rights Reserved. 粤ICP备2021057165号
IPv6 network supported